Experimental Investigation of Cooling Capacity of 4K GM Cryocoolers in Magnetic Fields
Physics Procedia2015Vol. 67, pp. 474–478
Citations Over TimeTop 25% of 2015 papers
Abstract
4K GM cryocoolers are inevitably exposed to the magnetic field inMRI systems. The cooling capacity of a 4K GM cryocooler is strongly dependent on the heat capacity of the magnetic regenerator materials, such as HoCu2, Er3Ni and Gd2O2S(GOS). In order to clarify the effect of the magnetic field on acryocooler's performance, we measured the cooling capacity of Sumitomo Heavy Industries, Ltd. (SHI) 1W 4K GM cryocoolers in magnetic fields up to 2.0 T. It is found that the impact of a magnetic field on the cooling capacity with a HoCu2/GOS hybrid regenerator is much smaller than that with a HoCu2 regenerator.
Related Papers
- → Experimental Investigation of Cooling Capacity of 4K GM Cryocoolers in Magnetic Fields(2015)14 cited
- → Cooling Performance of a Small GM Cryocooler with a New Ceramic Magnetic Regenerator Material(2003)20 cited
- → Development of 2W Class 4K Gifford-McMahon Cycle Cryocooler(1997)7 cited
- → Development of two-stage 4K cryocooler with modified Solvay cycle(1997)2 cited
- → Experimental Study of a 4 K Pulse Tube Cryocooler(2002)1 cited